TITLE 20         

APPENDIX B

Sections:

International Building Code Revisions
International Residential Code Revisions
Uniform Mechanical Code Revisions
Uniform Plumbing Code Revisions
National Electric Code Revisions
International Fire Code Revisions

International Building Code Revisions

     109.3 Required inspections.
     Section 109.3 of the International Building Code is amended to read as follows:
     109.3 Required inspections. The building official, upon notification, shall make the inspections set forth in Sections 109.3.1 through 109.3.10. (Ord. 1131, 2005)

      109.3.1 Footing and foundation inspection: Footing and foundation inspections shall be made after excavations for footings are complete and any required reinforcing steel is in place. For concrete foundations, any required forms shall be in place prior to inspection. Materials for the foundation shall be on the job, except where concrete is ready mixed in accordance with ASTM C 94, the concrete need not be on the job. (Ord. 1131, 2005)

      109.3.2 Concrete slab and under-floor inspection: Concrete slab and under-floor inspections shall be made after in-slab or under-floor reinforcing steel and building service equipment, conduit, piping accessories and other ancillary equipment items are in place, but before any concrete is placed or floor sheathing installed, including the sub-floor. (Ord. 1131, 2005)

      109.3.3 Lowest floor elevation: In flood hazard areas, upon placement of the lowest floor, including the basement, and prior to further vertical construction, the elevation certification required in Section 1612.5 shall be submitted to the building official. (Ord. 1131, 2005)

      109.3.4 Exterior shear-wall inspection: To be made prior to the application of exterior siding or cover. (Ord. 1131, 2005)

      109.3.5 Frame inspection: Framing inspections shall be made after the structure is dried-in, exterior windows installed, roof deck or sheathing and weather protected, all framing has been completed along with all fire blocking, all penetrations have been installed and sealed, chimneys and vents to be concealed are complete and the rough electrical, plumbing, mechanical ducting, heating wires are completed and ready for required testing. (Ord. 1131, 2005)

      109.3.6 Insulation inspection: To be made after frame inspection has been approved or certification issued by a Nevada licensed insulation contractor. (Ord. 1131, 2005)
109.3.7 Lath and gypsum board inspection: Lath and gypsum board inspections shall be made after lathing and gypsum board, interior and exterior, is in place, but before any plastering is applied or gypsum board joints and fasteners are taped and finished. (Ord. 1131, 2005)

      109.3.8 Fire-resistant penetrations: Protection of joints and penetrations in fire-resistance-rated assemblies shall not be concealed from view until inspected and approved. (Ord. 1131, 2005)


      109.3.9 Energy efficiency inspections: Inspections shall be made to determine compliance with Chapter 13 and shall include, but not limited to, inspections for: envelope insulation R and U values, penetration U value, duct system R value, and HVAC and water-heating equipment efficiency. (Ord. 1131, 2005)

      109.3.10 Other inspections: In addition to the inspections specified above, the building official is authorized to make or require other inspections of any construction work to ascertain compliance with the provisions of this code and other laws that are enforced by the Building Department. (Ord. 1131, 2005)

      109.3.11 Special inspections: For special inspections, see IBC Section 1704. (Ord. 1131, 2005)

      109.3.12 Final inspection: The final inspection shall be made after all work required by the building permit is completed. (Ord. 1131, 2005)

      111.4 Newly constructed separately owned multiple residential and commercial buildings.
      Section 111 of the IBC is amended by adding a new subsection as follows:
      Section 111.4. Construction of buildings for separately owned multiple commercial and residential condominiums on a single lot must comply with the following:
      1. Each unit must have a separate electric meter and an accessible disconnect.
      2. Each unit must have a separate water service and an accessible shut-off.
      3. Each unit must have a separate heating system.
      4. Where gas or propane is provided for use each unit must have a separate service and accessible shut-off. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 558, 1992)

      901.8. Automatic fire extinguishing systems--Special provisions.
Section 901 of the IBC is amended by adding new subsections as follows:
      901.8 All buildings or structures outside the jurisdiction of the Tahoe-Douglas Fire Protection District having a total building area of 5,000 square feet or more, and all buildings or structures three stories high or in excess of 45 feet in height, whichever is less, must be provided with automatic fire sprinkler protection, except as provided for in this section.
      Exceptions. New buildings or structures designated as R-3, Group U occupancies are exempted from the sprinkler system requirements. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 543, 1991; Ord. 517, 1990; Ord. 491, 1989; Ord. 437, 1985)

      901.8.1 No other exceptions to the requirements of section 901.8 will be permitted except by the approval of the building official and fire marshal. If the building official or fire marshal do not approve, no exception will be allowed unless approved by majority of the building and fire board of appeals. In instances where buildings or structures are exempted from the requirements of section 901.8 by the approval of the building official and fire marshal or an affirmative vote of the board of appeals, the buildings or structures must be equipped with an acceptable alternate method of providing fire protection. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 491, 1989; Ord. 437, 1985)

      901.8.2 Installation, inspection, maintenance and testing of sprinkler systems or any alternative extinguishing system approved pursuant to section 901.8.1 must meet the requirements set forth in the current edition of the National Fire Protection Association (“NFPA”) standard for the installation of sprinkler systems, NFPA 13, 13D, or 13R as applicable. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 491, 1989; Ord. 437, 1985)

      901.8.3 Total building area is defined for the purpose of this section as the total floor area in square feet for all floor levels within the exterior walls, or under the horizontal projection of the roof of a building. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 491, 1989; Ord. 437, 1985)

      901.8.4 All new buildings within the jurisdiction of the Tahoe-Douglas Fire Protection District must be provided with automatic fire sprinkler protection except for the following exemptions.
      1. Single family dwellings less than 5,000 square feet in floor area. Attached accessory uses must be included in calculations of floor area.
      2. Single family dwellings of 5,000 square feet in floor area or more if it meets all conditions of minimum fire flow, fire department access and NFPA 299 regulations. Attached accessory uses must be included in calculations of floor area.
      3. Buildings other than single-family residences and private garages, having a floor area less than 800 square feet and being classified as a light hazard occupancy as listed in the IBC
The exceptions must not reduce or eliminate any requirements for fire-extinguishing systems found in chapter 9 of the IBC. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 573, 1992; Ord. 543, 1991; Ord. 517, 1990)


     901.8.5 All existing buildings within the jurisdiction of the Tahoe-Douglas Fire Protection District must be provided with automatic fire sprinkler protection when changing use or when increasing the total floor area except for the following exceptions.
      1. Single family dwellings when the total floor area is less than 5,000 square feet. Attached accessory uses must be included in calculations of floor area.
      2. Single family dwellings of 5,000 square feet in floor area or more if it meets all conditions of minimum fire flow, fire department access and NFPA 299 regulations. Attached accessory uses must be included in calculations of floor area.
      3. Buildings other than single-family residences and private garages, having a floor area less than 800 square feet and being classified as a light hazard occupancy as listed in IBC.
The exceptions must not reduce or eliminate any requirements for fire-extinguishing systems found in chapter 9 of the IBC. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 573, 1992; Ord. 543, 1991; Ord. 517, 1990)

      901.8.6 No other exceptions to the requirement of sections 901.8.4 and 901.8.5 will be permitted except by an affirmative majority vote of the board of appeals. To grant an exemption the board of appeals must either: (i) require the buildings of structures to have an alternative extinguishing system, or (ii) require an acceptable alternative method of providing fire protection which will provide additional safety for occupants, better access for the fire department and other improved fire safety conditions when the board makes the finding that the exemption is based on low risk to life safety and property value. No exemption is allowed by the board of appeals unless the building or structure meets the minimum requirements of the IBC. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 517, 1990)

      901.8.7 Installation, inspection, maintenance and testing of sprinkler systems or any alternative extinguishing system approved pursuant to section 901.8.6 must meet the requirements as set forth in the current edition of the NFPA standard for the installation of sprinkler systems, NFPA 13, 13D, or 13R, as applicable. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 517, 1990)

      901.8.8 Total building area is defined for the purpose of this section as the total floor area in square feet for all floor levels within the exterior walls, or under the horizontal projection of the roof of a building.  (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord 573, 1992; Ord. 543, 1991; Ord. 517, 1990)     

      Chapter 9 of the IBC is amended by adding the following section:

      912 Emergency Services Communications

      

       912.2 When required.
Except as otherwise provided in this section, no person or entity shall construct or develop any commercial or industrial building or structure that fails to support adequate radio coverage for emergency service workers, including but not limited to, firefighters and police officers.
These provisions apply to:
      1. New buildings and structures greater than 50,000 square feet (for purposes of this section area separation walls cannot be used to define separate buildings).
      2. All basements more than 10,000 square feet, where the design occupant load is greater than 50, regardless of the occupancy.
      3. Any building additions or remodel work that result in a building meeting the criteria in this section.
      4. Any additions or building remodels that exceeds $500,000.
      5. Any building that creates a “special hazard” for emergency services communications in addition to the normal hazard of the occupancy.
This requirement may be waived by the fire chief for fire operations and the sheriff for law
enforcement application but only with the concurrence of the communications director. (Ord. 1131, 2005; Ord. 1062, 2004)

      912.3 Definitions.
      1. Enhanced amplification system: The equipment to provide adequate signal strength to achieve the required adequate radio coverage, including: radiating cable systems, internal multiple antenna systems with a frequency range established by Douglas County, with amplification systems as needed, voting receiver system, or any other appropriate emergency service.
      2. Special hazard: Construction known to limit communications.
      3. Radio coverage: A successful two-way communications test between the building interior and the communications center for all appropriate emergency service providers for the building.
      4. Special Inspector: A communications technician appointed by the director of communication. (Ord. 1131, 2005; Ord. 1062, 2004)

      912.4 Performance requirements–Building interior.
      1. A minimum average field strength of -80 dBm throughout 90% of the area of each floor of the building when transmitted from the appropriate transmitter of the emergency service dispatch center that is providing fire and emergency medical protection services to the building.
      2. The following areas must be 100% covered at the minimum field strength of -80dBm: fire command centers, elevators, stairwells, protect-in-place areas, lobby refuge areas, equipment rooms, high hazard areas, basements, and underground parking areas.
      3. If the system requires electrical power for operation, it must have an independent battery or generator system capable of operating for a period of at least four hours without maintenance. This backup power system must be able to insure uninterrupted communications when external power is lost. (Ord. 1131, 2005; Ord. 1062, 2004)

      912.5 Guidelines for general measurements.
      1. FCC Authorization.
If electronic amplification is used in the system, all FCC authorizations must be obtained prior to the use of the system. A copy of these authorizations must be provided to the special inspector.
      2. Equipment.
          A. A calibrated service monitor (with a factory calibration dated within 24 months) with a service monitor using a unity gain antenna on a small ground plane.
          B. A unity gain vertically polarized ground-plane antenna. The ground plane must be 3 to 4 feet above the floor.
      3. Measurements.
      Three measurements of filed strength must be made at each location. If measurements vary, an average measurement may be used.
      4. Confirmation.
      The special inspector must do a hands-on radio test of selected area locations to check for intelligibility of the communications. Garbling of communications due to reflections, multipath, or other propagation conditions takes precedence over signal strength measurements.
      5. Radio frequency field strength information.
          A. Location, elevation, date, and time of field strength test.
          B. The persons or entity conducting the tests.
          C. Map showing location of all government transmitters in relation to the building, including their height and distance.
          D. List of frequencies and antenna bandwidth calculations.
          E. Copies of FCC Licenses for frequencies.
          F. Field strength test results for each receiver location. (Ord. 1131, 2005; Ord. 1062, 2004)

      912.6 Initial tests.
      1. Before a certificate of occupancy may be issued for a building that must meet the requirements of this section, an initial test plan must be submitted to the special inspector for approval and a successful completion of the test. The plan must contain:
      2. Initial tests:
All testing must be done under the supervision of the special inspector.
          A. Signal strength, both inbound and outbound as defined above, must be measured on each and every floor above and below ground, including stairwells, basements, penthouse facilities, and parking areas of the structure.
          B. The structure must be divided into 100-foot grids with the measurements taken at the approximate center of each grid. In critical areas that require 100% coverage, the grids must be reduced to 25 feet. In areas where displays, equipment, stock, or any other obstruction may significantly affect communications, the size of the grids may also be further reduced upon recommendations by the special inspector.
          C. A spot located approximately in the center of a grid area will be selected for the test. If this location fails, the grid is marked failed. Other locations within the grid cannot be substituted to pass the test.
          D. The test must be conducted using a portable hand-held radio approved by the special inspector.
          E. Two-way communications to and from the outside of the building through dispatch will be used.
          F. Each grid area will be tested for transmission and reception; minimum signal strength of
-80 dBm. If signal strength fails to meet the requirement, the grid area must be marked as a fail.
          G. The gain values of all amplifiers must be measured and the test measurement results must be kept on file at the facility and the fire department. These measurements must be verified each year during the annual tests. If the measurement results are lost, the building owner will be required to rerun the acceptance test to reestablish the gain values. (Ord. 1131, 2005; Ord. 1062, 2004)

      912.7 Annual tests by property owner.
      The property owner must conduct an annual test of all active components of the system, including but not limited to, amplifiers, power supplies, and backup batteries a minimum of once every 12 months. Amplifiers must be tested to ensure that the gain is within .5 dB of the power at the time of installation. Backup batteries and power supplies must be tested under load for a period of 1 hour. If, at the end of the test period, the output power of the amplifier has decreased by more than .5 dB, the system will have failed the test. If the special inspector requires, the test may be extended for additional 1-hour periods until the testing technician confirms the integrity of the backup unit. All other active components must be checked to determine that they are operating within the manufacturer’s specifications for the intended purpose. (Ord. 1131, 2005; Ord. 1062, 2004)

      912.8 Annual tests by emergency services agencies.
      Annual tests must also be conducted by the emergency services agencies or their designated representatives. These tests will be a subset of the initial tests. If the tests fail to demonstrate adequate system performance, the owner of the building or structure will be required to restore the system in a manner consistent to meet the original approval criteria. If the degradation to the system is due to new building additions, or remodeling, the owner of the building or structure will be required to restore the system to meet the original approval criteria in order to obtain a final inspection for occupancy. (Ord. 1131, 2005; Ord. 1062, 2004)

      1019.1.7 Stairway numbering system.
      Section 1019.1.7 of the IBC is amended by adding the following language:
All signs on doors leading to stairways that extend to the roof must be green in color. All other signs on doors leading to stairways must be red in color. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 437, 1985)


     1503.1 Weather protection.
     Section 1503.1 of the IBC is amended by adding the following language: Roof decks shall be covered with approved roof coverings secured to the building or structure in accordance with the provisions of this chapter. Roof coverings shall be designed, installed and maintained in accordance with this code and the approved manufacturer’s instructions such that the roof covering shall serve to protect the building or structure. Roof ice build-up protection is required at an elevation of 5,300 feet and above throughout the County. (Ord. 1131, 2005)

      1507 Roof covering materials and application.
      Section 1507 of the IBC is amended by adding the following language to section 1507.8 to apply to all structures within the jurisdiction of the Tahoe Douglas Fire Protection District. (Ord. 1131, 2005; Ord. 1112, 2005)

      1507.8 Class A roofing materials required in Tahoe Douglas Fire Protection District.
      1. All new roofs in the Tahoe Douglas Fire Protection District must have Class “A” material applied. Built up roofing that has a mineral surface may have Class “B” material. A person may not apply nonrated roofing or shingle siding materials, such as wood shakes or shingles, on any new construction or subsequent reapplication.
      2. Reroofing and repairs where more than 25 percent of the roof area is under construction or replacement must meet all the provisions of this section for new construction. Where the reroofing or repairs is less than 25 percent of the roof area, matching the existing materials may be permitted provided any wood product, such as wood shake or shingle material, is a Class “B” pressure treated product. This exception may be allowed only once per structure.
      3. Wood shake or shingle siding material may not be applied to the exterior surface of a structure within 8 feet of the adjacent ground level, and wood shingle siding material may not exceed 10 percent of the total area of the structure side. Wood shake or shingle siding must be Class “B” or better materials. Wood shingle siding presently in existence may be repaired only with Class “B” rated materials. (Ord. 1131, 2005; Ord. 1112, 2005)

      1608 Snow loads.
      Section 1608.1 of the IBC is amended by adding the following language:
      For areas in Douglas County above 6,000 feet elevation, roof live loads are 150 pounds per square foot throughout. Elsewhere in county, roof live loads are 30 pounds per square foot throughout. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 437, 1985)


      1609.3 Basic wind design.
      Section 1609.3 of the IBC, is amended by substituting the following language:
      The minimum basic wind speed at any site in the County is 105 miles per hour (three second gust) for determining design wind pressure. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994, Ord. 558, 1992)

      1609.4 Exposure category.
      Section 1609.4 of the IBC, first paragraph, is amended to read as follows:
An exposure of "C" shall be used as a minimum in the design of all structures within the County. All structures within ¼ mile from the shoreline at Lake Tahoe shall be designed as minimum exposure "C". Exposure B may be used for all structures in the Lake Tahoe basin area between ¼ mile of the lake and below the elevation of 7200 feet and meeting the requirements of exposure B.
      When applying the simplified wind load method, a single exposure category shall be used based upon the most restrictive for any given wind direction. (Ord. 1131, 2005)

      1802.1 Foundation and soils investigation--General.
      Section 1802.1 of the IBC is amended by adding the following sentence:
      The building official may require a soils investigation and foundation engineering on construction sites sloping in excess of 15 percent. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 437, 1985)

      1805.1 Footings and foundations.
      Section 1805.1 of the IBC is amended to read as follows:
      Footings and foundations, unless otherwise specifically provided, shall be constructed of masonry, concrete or treated wood in conformance with International Building Code and shall in all cases extend below the frost line. Footings of concrete and masonry shall be of solid material. Foundations supporting wood shall extend at least 6 inches (152 mm) above the adjacent finish grade. (Ord. 1131, 2005)

     1805.2: Frost line.

     Section 1805.2 of the IBC is amended by adding the following sentence:
     The frost line referred to shall be defined as 24 inches below finished grade, at elevations of 6,000 feet or more and 18” below finished grade at elevations of less than 6,000 feet. (Ord. 1131, 2005)

      Table 1805.4.2: Foundations for stud bearing walls.
      Table 1805.4.2 of the IBC is amended to read as follows:

TABLE 1805.4.2 FOUNDATIONS FOR STUD BEARING WALLS
MINIMUM REQUIREMENTS 1, 2, 3, 4, 5

Number of
Stories
Supported by
the Foundations
Minimum Thickness
of Foundation
Wall (Inches)

Minimum
Width
of Footing
(Inches)
Minimum
Thickness of Footing
(Inches)
Minimum
Depth of Foundation
Below
Natural
Surface of
Ground and
Finish Grade
(Inches)
 
Concrete
    Unit
    Masonry
     
1
8
8
16
8
18
2
8
8
16
8
18
3
10
10
18
10
18


1. Where unusual conditions or frost conditions are found, footings and foundations shall be as required in Section 1806.1.
2. The ground under the floor may be excavated to the elevation of the bottom of the footing.
3. Foundations may support a roof in addition to the stipulated number of floors. Foundations supporting roofs only, shall be as required for supporting one floor.
4. Foundations may support a roof in addition to the allowed number of floors. Foundations supporting roofs only must be the same as those required for supporting one floor.
5. Exterior non-bearing walls must be supported by a foundation. Foundations supporting exterior non-bearing walls must be the same as those required for supporting one floor. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641 1994; Ord. 558, 1992; Ord. 437, 1985)

      1805.10 Weathered foundations.
      Section1805 is amended by adding a new subsection1805.10 to read as follows:
      1805.10 Any foundation which has weathered through two or more winters without any structure built on it to give protection must have an inspection by a structural engineer licensed by the State of Nevada who must certify that the foundation is structurally sufficient to carry the load to be imposed on it, or certify specifications necessary for repairs which may be required to bring it to an acceptable condition where it will adequately support the structure to be built upon it. (Ord. 1131, 2005)

      2304.9.1: Fastener requirement.
      Section 2304.9.1 of the IBC is amended to read as follows:
      Connections for wood members shall be designed in accordance with the appropriate methodology in Section 2301.2. The number and size of nails connecting wood members shall not be less than that set forth in Table 2304.9.1. Roof trusses and rafter ties shall be fastened to the top plate at all points of bearing by approved truss ties. (Ord. 1131, 2005)

      2903 Temporary toilets.
      Chapter 29 of the IBC is amended by adding the following section:
      Section 2903 During construction, unless alternative facilities are made available, temporary toilets must be provided on the basis of the following rate of toilets to the number of workers on the job at a ratio of one for each 30 workers. In addition, urinals must be provided on the basis of one for each 30 men. The toilets must be available within 300 feet of the structure under construction. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 558, 1992; Ord. 437, 1985).

      3001 Elevators and conveying systems.
      Section 3001.1 of the IBC is amended to read as follows:
      The provisions of this chapter shall apply to the design, installation, operation, alteration and repair of elevators, dumbwaiters, escalators and moving walks and their hoist ways. Additional provisions may be required, regulated and enforced through chapter 618 of the Nevada Revised Statutes and NAC 618.400 - 618.507 by the State of Nevada Department of Business and Industry. When conflicts arise between the provisions of the International Building Code, chapter 30 and NRS chapter 618, the most restrictive shall govern. (Ord. 1131, 2005)

      3103 Temporary structures.
      Section 3103.1 of the IBC is amended by adding:
      Temporary construction facilities, which are located on site in conjunction with valid building permits and occupied by job site personnel, which have connection only to electrical power, may be exempt from the provisions of section 3103. (Ord. 1131, 2005)


     3313 Safety and security.
     Chapter 33 of the IBC is amended by adding a new section as follows:
     Section 3313. The building official may require fencing around the construction site to make the property safe for the public. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 437, 1985).

      3314 Debris on construction site.
      Chapter 33 of the IBC is amended by adding a new section as follows:
      Section 3314. All debris on construction sites must be contained and removed periodically as required for safety and cleanliness. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 437, 1985)

      3406.4 Conversion of existing buildings into separately owned multiple commercial and residential buildings.

      Section 3406 of the IBC is amended by adding the following subsection:
      Section 3406.4 Conversion of existing buildings to separately owned multiple commercial and residential condominiums on a single lot must comply with the following:
          1. Each unit must have a separate electric meter and an accessible disconnect.
          2. Each unit must have a separate water service and an accessible shut off.
          3. Each unit must have a separate heating system.
          4. Where gas or propane is provided for use each unit must have a separate service and accessible shut off. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 558, 1992)


IBC APPENDIX Amendments.


      Appendix I104.2 Patio covers-Footings.
      I104.2 of the IBC is amended to read as follows:
      A patio cover is permitted to be supported on a concrete slab on grade without footings, provided the slab conforms to the provisions of Chapter 19 of this code, is not less than 3-1/2 inches thick and further provided that the columns do not support loads in excess of 750 pounds (3.36 kN) per column. (Ord. 1131, 2005)

  

INTERNATIONAL RESIDENTIAL CODE

     Table R301.2 (1): Climatic and geographic design criteria.
     Table R301.2 (1) of the IRC is amended to read as follows:

TABLE R301.2 (1)

CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA

 

 

 

GROUND

SNOW

LOAD

 

 

 

WIND

SPEED

(mph)

 

 

 

SEISMIC

DESIGN

CATE-GORY

 

SUBJECT TO DAMAGE FROM

 

 

 

WINTER

DESIGN

TEMP

 

 

 

ICE

SHIELD

UNDER-LAYMENT

REQUIRED

 

 

 

FLOOD

HAZARDS

 

 

 

AIR

FREEZ-ING

INDEX

 

 

 

MEAN

ANNUAL

TEMP

 

Weather-ing

 

Frost line

depth

 

Termite

 

Decay

 

See Amended Sec 1608.2

 

105

 

D2

D2

 

SEVERE

SEVERE

 

24” > 6,000 ft. elev., 18”< 6,000 elev. ft.

 

MODER-ATE

TO

HEAVY

 

NONE

TO

SLIGHT

 

10° F

 

YES

ABOVE

6000 '

 

SEE

TITLE 20 CHAPTER 20.50

 

594

 

49.4°F

 

(Ord. 1131, 2005)

      R309.1 Opening protection.
      Section R309.1 of the IRC is amended to read as follows:
      Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and residence shall be equipped with self closing solid wood doors not less than 1 3/8 inches in thickness, self closing solid or honeycomb core steel doors not less than 1 3/8 inches thick, or self closing 20-minute fire-rated doors. (Ord. 1131, 2005)

      R309.2 Separation required.
      Section R309.2 of the IRC is amended to read as follows:
      The garage shall be separated from the residence and its attic area by not less than 5/8 inch type “X” gypsum board applied to the garage side. Garages beneath habitable rooms shall be separated from all habitable rooms above by not less than 5/8 inch type “X” gypsum board of equivalent. Where the separation is a ceiling assembly, the structure supporting the separation shall also be protected by not less than 5/8 inch type “X” gypsum board or equivalent. (Ord. 1131, 2005)

      R309.7 Driveways.
      Section R309 of the IRC is amended by adding a new subsection as follows:
      R309.7 For every private access from a public provided with a driveway, the driveway must not exceed a maximum gradient between vertical transitions of 14% (i.e., 1¾ vertical inches per horizontal foot), this maximum gradient shall be determined from the proposed finish garage floor elevation to the public-way or street access. The alignment must be safe and convenient to back a car out, or an adequate turnaround must be provided. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 437, 1985).

      R311.2.2 Under stair protection.
      Section R311.2.2 of the IRC is amended to read as follows:
      Enclosed accessible space under stairs shall have walls, under stair surface and any soffits
protected on the enclosed side with 5/8 inch type “X” gypsum board. (Ord. 1131, 2005)

      Table R403.1: Minimum footing and foundation requirements.
      Table R403.1 of the IRC is amended to read as follows:

   TABLE R403.1 MINIMUM FOOTING & FOUNDATIN REQUIREMENTS 1, 2, 3, 4, 5

 

Number of

Stories

Supported by

the Foundations

 

Minimum Thickness

of Foundation

Wall (Inches)

 

Minimum

Width

of Footing

(Inches)

 

Minimum

Thickness

of Footing

(Inches)

 

Minimum

Depth of Foundation

Below

Natural

Surface of

Ground and

Finish Grade

(Inches)

 

 

 

Concrete

 

Unit

Masonry

 

 

 

 

 

 

 

  1

 

  8

 

  8

 

  16

 

  8

 

  18

 

  2

 

  8

 

  8

 

  16

 

  8

 

  18

 

  3

 

  10

 

  10

 

  18

 

  10

 

  18

1. Where unusual conditions or frost conditions are found, footings and foundations shall be as required in Section R403.1.4.1.
2. The ground under the floor may be excavated to the elevation of the bottom of the footing.
3. Foundations may support a roof in addition to the stipulated number of floors. Foundations supporting roofs only, shall be as required for supporting one floor.
4. Foundations may support a roof in addition to the allowed number of floors. Foundations supporting roofs only must be the same as those required for supporting one floor.
5. Exterior non-bearing walls must be supported by a foundation. Foundations supporting exterior non-bearing walls must be the same as those required for supporting one floor. (Ord. 1131, 2005, Ord. 802, 1998; Ord. 711, 1995; Ord. 641 1994; Ord. 558, 1992; Ord. 437, 1985)

      R403.1.1 Minimum footing size.
      Section R403.1.1 is amended by adding the following language:
      Minimum footing dimension shall be specified in IBC Table 1805.4.2. There shall be a minimum of one #4 continuous reinforcing bar in the top a of all foundation walls, and one #4 continuous reinforcing bar in the footing. When the footing and foundation wall are placed separately or when the foundation wall exceeds 24 inches in height, #4 vertical bars, at 48 inches on center (48" O/C) or 32 inches on center when using concrete block, shall be used to connect the footing with the foundation wall. When engineering data is provided, the footing and foundation wall steel requirements may be reduced. Foundation walls greater then 48 inches in height shall be designed by a Nevada professional engineer. (Ord. 1131, 2005)

      R1007 Appliance emissions.

      Chapter 10 of the IRC is amended by adding the following sections:
      R1007.1 General. No person shall install any wood burning stove or fireplace insert that emits more than the emission standards set by this section. A permit shall not be issued to any person who wishes to install a wood burning stove or fireplace insert that does not meet the emission standards of this section. (Ord. 1131, 2005)

      R1007.2 Certification.

      Each wood burning stove or fireplace insert shall bear a certification from the manufacturer that the appliance meets the emission standards set forth in this section. (Ord. 1131, 2005)

      R1007.3 Standards.

      Wood burning stove and fireplace inserts certified to meet the emission standards set by United States Environmental Protection Agency under 40 CFR Part 60 are deem in compliance with the requirements of this section. (Ord. 1131, 2005)

      R1007.4 Required emissions.

      For wood burning stoves and fireplace inserts the minimum emissions are as follows: For non-catalytic appliances the emissions shall not exceed 7.5 grams, for catalytic equipped appliances the emissions shall not exceed 4.1 grams. (Ord. 1131, 2005)

      N1104 Service water heating.

      Section N1104 of the IRC is amended by adding the following subsection:
      N1104.2 Hot water piping insulation. All piping serving as part of a hot water system installed in unconditioned areas shall be protected with a minimum R-2. Insulation shall be installed continuously from within 2 feet of the water heater to within 2 feet of the fixture or outlet. Insulation may be omitted when passing through a restricted opening in framing members. (Ord. 1131, 2005)

      G2401.1 (101.2) Application.
      Section G2401.1 (101.2) of the IRC is amended to read as follows:
      This chapter covers those fuel gas piping systems, fuel-gas utilization equipment and related accessories, venting systems and combustion air configurations most commonly encountered in the construction of one- and two-family dwellings and structures regulated by this code.

     Exception: As an alternative to the provisions of this code, fuel-gas piping systems, fuel-gas utilization equipment and related accessories in existing buildings that are undergoing repairs, alterations, changes in occupancy or construction of additions shall be permitted to comply with the provisions of the International Existing Building Code. 

     Coverage of piping systems shall extend from the point of delivery to the outlet of the equipment shutoff valves (see Point of Delivery). Piping systems requirements shall include design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance. Requirements for gas utilization equipment and related accessories shall include installation, combustion and ventilation air and venting and connections to piping systems.
     The omission from this chapter of any material or method of installation provided for in the International Fuel Gas Code shall not be construed as prohibiting the use of such material or method of installation. Fuel-gas piping systems, fuel-gas utilization equipment and related accessories, venting systems and combustion air configurations not specifically covered in these chapters shall comply with the applicable provisions of the International Fuel Gas Code.
     Gaseous hydrogen systems shall be regulated by Chapter 7 of the International Fuel Gas Code.
     This chapter shall not apply to the following:
     1. Liquefied natural gas (LNG) installations.
     2. LP-gas piping for buildings.
     3. Except as provided in Section G2412.1.1, gas piping, meters, gas pressure regulators, and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP-gas.
     4. Portable LP-gas equipment of all types that is not connected to a fixed fuel piping system.
     5. Portable fuel cell appliances that are neither connected to a fixed piping system nor interconnected to a power grid.
     6. Installation of hydrogen gas, LP-gas and compressed natural gas (CNG) systems on vehicles. (Ord. 1131, 2005)

      P2503.7: Inspection and testing of backflow prevention devices.
      Section P2503.7 of the IRC is amended to read as follows:
      Inspection and testing of backflow prevention devices shall comply with Section P2503.7.1 and Section P2503.7.2. (Ord. 1131, 2005)

      P2503.7.1 Inspections.

      Inspections shall be made of all backflow prevention assemblies to determine whether they are operable. (Ord. 1131, 2005)

      P2503.7.2 Testing.
      The owner of the premises or the responsible person shall have the backflow prevention assembly tested by a certified backflow assembly tester at the time of installation, repair or relocation and at least annually thereafter unless required more frequently by the water purveyor, or utility or the State Health Department. The periodic testing shall be performed in accordance with procedures referenced in the University of Southern California manual of Cross-Connection Control (Ninth Edition) by a tester qualified in accordance with those standards and with the standards in the CA-NV section of the AWWA backflow prevention assembly testers and cross-connection control program. (Ord. 1131, 2005)

      P2603.6: Freezing.

      Section P2603.6 of the IRC is amended to read as follows:
      In localities having a winter design temperature of 32ºF (0ºC) or lower as shown in Table R301.2 (1) of this code, a water, soil or waste pipe shall not be installed outside of a building, in exterior walls, in attics or crawl spaces, or in any other place subjected to freezing temperature unless adequate provision is made to protect it from freezing by insulation or heat or both. Water service pipe shall be installed not less than 6 inches (762 mm) deep below the frost line. (Ord. 1131, 2005)

      P2903.3.1: Maximum pressure.
      Section P2903.3.1 of the IRC is amended to read as follows:
      Maximum static pressure shall be 80 psi (551 kPa). When main pressure exceeds 65 psi (448 kPa), an approved pressure-reducing valve conforming to ASSE 1003 preceded by an adequate strainer shall be installed and the static pressure reduced to sixty one (61) pounds per square inch (421 kPa) or less. Where pressure regulators are required, the pressure regulator shall be installed between the source of water and after the meter and back-flow prevention device (if installed at the meter), and before all exterior and interior fixtures and outlets.
     For potable water services up to and including one and one-half (1-½) inch regulators, provision shall be made to prevent pressure on the building side of the regulator from exceeding main supply pressure. Approved regulators with integral bypasses shall be acceptable. Each such regulator and strainer shall be accessibly located and shall have the strainer readily accessible for cleaning without removing the regulator or strainer body or disconnecting the supply piping. Pressure regulators shall not be the type that can be adjusted to provide static water pressure more than seventy five (75) pounds per square inch (518 kPa). (Ord. 1131, 2005)

     P2903.7 Size of water-service mains, branch mains, and risers.

     Section P2903.7 of the IRC is amended to read as follows:
     The minimum size water service pipe shall be ¾ inch. The size of water service mains, branch mains and risers shall be determined according to water supply demand [gpm (L/m)], available water pressure [psi (kPa)] and friction loss due to the water meter and developed length of pipe [feet (m)], including equivalent length of fittings. The size of each water distribution system shall be determined according to the procedure outlined in this section or by other design methods conforming to acceptable engineering practice and approved by the administrative authority:
      1. Obtain the minimum daily static service pressure [psi (kPa)] available (as determined by the local water authority) at the water meter or other source of supply at the installation location. Adjust this minimum daily static pressure [psi (kPa)] for the following conditions:
      1.1. Determine the difference in elevation between the source of supply and the highest water supply outlet. Where the highest water supply outlet is located above the source of supply, deduct 0.5 psi (3.4 kPa) for each foot of difference in elevation. Where the highest water supply outlet is located below the source of supply, add 0.5 psi (3.4 kPa) for each foot of difference in elevation.
      1.2. Where a water pressure reducing valve is installed in the water distribution system, the minimum daily static water pressure available is 80 percent of the minimum daily static water pressure at the source of supply or the set pressure downstream of the pressure reducing valve, whichever is smaller.
      1.3. Deduct all pressure losses due to special equipment such as a backflow preventer, water filter and water softener. Pressure loss data for each piece of equipment shall be obtained through the manufacturer of such devices.
      1.4. Deduct the pressure in excess of 8 psi (55 kPa) due to installation of the special plumbing fixture, such as temperature controlled shower and flushometer tank water closet. Using the resulting minimum available pressure, find the corresponding pressure range in Table P2903.7.
      2. The maximum developed length for water piping is the actual length of pipe between the source of supply and the most remote fixture, including either hot (through the water heater) or cold water branches multiplied by a factor of 1.2 to compensate for pressure loss through fittings. Select the appropriate column in Table P2903.7 equal to or greater than the calculated maximum developed length.
      3. To determine the size of water service pipe, meter and main distribution pipe to the building using the appropriate table, follow down the selected maximum developed length column to a fixture unit equal to, or greater than the total installation demand calculated by using the combined water supply fixture unit column of Table P2903.6. Read the water service pipe and meter sizes in the first left-hand column and the main distribution pipe to the building in the second left-hand column on the same row.
      4. To determine the size of each water distribution pipe, start at the most remote outlet on each branch (either hot or cold branch) and, working back toward the main distribution pipe to the building, add up the water supply fixture unit demand passing through each segment of the distribution system using the related hot or cold column of Table P2903.6. Knowing demand, the size of each segment shall be read from the second left-hand column of the same table and a maximum developed length column selected in Steps 1 and 2, under the same or next smaller size meter row. In no case does the size of any branch or main need to be larger than the size of the main distribution pipe to the building established in Step 3.
      5. The size of pipes from the hot water heater and all hot water branches shall not less than the minimum size necessary to meet the water supply requirements, as outlined in this section.
      6. All above determinations shall be clearly noted on the plans, specifications, drawings or a worksheet submitted to the Administrative Authority whenever pipes from the hot water heater exceed one half (½) inch in diameter. (Ord. 1131, 2005)

      P3005.4 Drain pipe sizing.
      Section P3005.4 of the IRC is amended to read as follows:
      Drain pipes shall be sized according to drainage fixture unit (d.f.u.) loads. The size of the drainage piping shall not be reduced in size in the direction of flow. The following general procedure is permitted to be used:
      1. Draw an isometric layout or riser diagram denoting fixtures on the layout.
      2. Assign d.f.u. values to each fixture group plus individual fixtures using Table P3004.1.
      3. Starting with the top floor or most remote fixtures, work downstream toward the building drain accumulating d.f.u. values for fixture groups plus individual fixtures for each branch. Where multiple bath groups are being added, use the reduced d.f.u. values in Table P3004.1, which take into account probability factors of simultaneous use.
      4. Size branches and stacks by equating the assigned d.f.u. values to pipe sizes shown in Table P3005.4.1.
      5. Determine the pipe diameter and slope of the building drain and building sewer based on the accumulated d.f.u. values, using Table P3005.4.2, but in no event shall the building sewer be less than four (4) inches in diameter. (Ord. 1131, 2005)

      P3009 Private sewage disposal system.
      Section P3009 of the IRC is amended by adding the following subsections:
      P3009.1 Private system.
      Whenever a private sewage disposal system is required, the type, size, construction and its location of the system must comply with the requirements of the State of Nevada Bureau of Health Protection. Examination and approval of any proposed private sewage disposal system by the State of Nevada Bureau of Health Protection or the authorized county inspector may be required before issuance of any permit. (Ord. 1131, 2005)

      P3009.2 Fees.
      A fee set by resolution of the board must be paid when application is made for a private sewage disposal system. (Ord. 1131, 2005)

      P3009.3 Engineered system.
      If a private sewage disposal system needs or requires an engineered design because of high ground water or percolation problems, an application for its approval must be submitted to the State of Nevada Bureau of Health Protection. After the application and the engineered system are approved by the State of Nevada Bureau of Health Protection, the applicant must secure a letter of approval from the agency. Upon submitting the letter of approval to the building official, the permit for the structure may be issued. Only after the State of Nevada Bureau of Health Protection has issued a written approval for the completion of the engineered system, the building official may issue a certificate of occupancy for the structure it serves. Douglas County assumes no responsibility whatsoever for the engineered system. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 439, 1985).

      E3501.1 Administrative Provisions.
      Section E3501.1 of the IRC is amended by adding the following:
      The administrative provisions of NFPA 70 Article 80 are adopted for use with this code. Where, in any specific case, a conflict occurs between this code and NFPA Article 80, the requirements of the most restrictive provision shall govern. (Ord. 1131, 2005)

      E3501.2 Number of services.
      Section E3501.2 of the IRC is amended by adding a subsection to read as follows:
      Properties determined to be one acre or less shall only be supplied by one service, unless special permission is granted by the Building Official in the form of a waiver.
      Exception: An accessory dwelling approved by the Douglas County Community Development Department, with the electrical service installed per E3301.8 and E3301.9. (Ord. 1131, 2005)

      E3501.6: Service disconnect required.
      Section E3501.6 of the IRC is amended to read as follows:
      The disconnecting means shall be physically installed and attached to the outside of the building or structure served or where the conductors pass through the building or structure. The disconnecting means shall be at a readily accessible location nearest the point of entrance of the conductors. For the purpose of this section, the requirements in NEC Article 230.6 shall be permitted to be utilized.
      Exception #1: Manufactured housing, as regulated by NRS 489 and NEC Article 550. When the disconnecting means is mounted independently of the manufactured structure, it shall be readily identified by a 6-inch equilateral triangle, red in color that complies with the Fire Code.
      Exception #2: The disconnecting means may be mounted independently of the structure served, when mounted in direct line of sight, but no greater than 50-feet from the structure, and the independent disconnecting means is identified by a red triangle that complies with the Fire Code. (Ord. 1131, 2005)

      E3501.6.1 Marking of service equipment and disconnects.
      Service disconnects shall be permanently marked as a service disconnect. Service equipment shall be listed for that purpose. Individual meter socket enclosures shall not be considered service equipment. (Ord. 1131, 2005)

      E3501.6.2 Service disconnect location.
      The service disconnecting means shall be installed at a readily accessible location outside of a building or other structure nearest the point of entrance of the service conductors. The service disconnecting means shall be located not more than 50 feet from the building or structure it serves. Installation of the disconnecting means shall not be more than 6’ (feet) – 6” (inches) above finish grade or front access level to the top of the operating handle. The feeder or supply conductors to a building or other structure, other than a detached Group U occupancy, when located more than 50 feet from the service disconnecting means, shall have an exterior disconnect placed at a point readily accessible nearest the point of entrance of the feeder conductor installed not more than 6 feet above finish grade or front access level to the top of the operating handle.
     Exception: The service disconnecting means may be installed within a building when an external, remote shunt trip switch is provided. All shunt trip switches shall be located a maximum of 6’ (feet) – 6” (inches) above finish grade at a location approved by the fire department. All shunt trip switches shall be located within a 6-inch equilateral triangle, red in color. Service disconnecting means shall not be installed in bathrooms. Each occupant shall have access to the disconnect serving the dwelling unit in which they reside. (Ord. 1131, 2005)

      E3501.8 Service group.
      Section E3501 of the IRC is amended by adding a subsection to read as follows:
      E3501.8 Service group. Multiple services, which supply more than one building or structure on the same property, shall be grouped together with distances between panels not to exceed 10 feet of separation, unless special permission is granted by the building official in the form of a waiver. (Ord. 1131, 2005)

      E3604.8 Feeder disconnect required.
      Section E3604 of the IRC is amended adding a subsection to read as follows:
      E3604.8 Feeder disconnect required. The disconnecting means shall be physically installed and attached to the outside of the building or structure served or where the conductors pass through the building or structure. The disconnecting means shall be at a readily accessible location nearest the point of entrance of the conductors. For the purpose of this section, the requirements in NEC Article 230.6 shall be permitted to be utilized.

     Exception #1: Manufactured housing, as regulated by NRS 489 and NEC Article 550. When the disconnecting means is mounted independently of the manufactured structure, it shall be readily identified by a 6-inch equilateral triangle, red in color that complies with the Fire Code.
     Exception #2: The disconnecting means may be mounted independently of the structure served, when mounted in direct line of sight, but no greater than 50-feet from the structure, and the independent disconnecting means is identified by a red triangle that complies with the Fire Code. (Ord. 1131, 2005)

      E3802.11 Bedrooms outlets.
      Section E3802.11 of the IRC is amended to read as follows:
With the exception of smoke detectors, carbon monoxide detectors, and home security systems installed on individual branch circuits, all branch circuits that supply 125-volt, single-phase, 15- and 20-ampere outlets installed in dwelling unit bedrooms shall be protected by an arc-fault circuit interrupter (AFCI) listed to provide protection of the entire branch circuit. (Ord. 1131, 2005)

      E4109.3 Accessibility.
      Section E4109.3 of the IRC is amended to read as follows:
Hydromassage bathtub electrical equipment access shall be on the same floor level as the bathtub. The electrical equipment shall be accessible without damaging the building structure or interior and exterior building finish, no access shall be allowed through the under floor. (Ord. 1131, 2005)

      H106.2 Footings.
      Section H106.2 of the IRC is added to read as follows:
      A patio cover shall be permitted to be supported on a concrete slab on grade without footings, provided the slab conforms to the provisions of Chapter 19 of this code, is not less than 3½ inches (89 mm) thick and further provided that the columns do not support loads in excess of 750 pounds (3.36 kN) per column. (Ord. 1131, 2005)

UNIFORM MECHANICAL CODE REVISIONS

      110  Appeals.
      Section 110 of the UMC is deleted and amended by substituting the following language:
      The building official’s determination of the suitability of alternate materials or other means of construction may be appealed to the building and fire board of appeals in accordance with section 20.810.040.  (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 641, 1994; Ord. 441, 1985)

   

      112.1  Permits.   
      Section 112.1 of the UMC is amended by adding the following language:
      A separate permit is not required under this code if a valid building permit has been issued under the IBC or IRC for the permitted structure.  (Ord. 802, 1998; Ord. 711, 1995; Ord. 441, 1985)   

      115.2  Fees.
      Section 115.2 of the UMC is deleted and the following language added:
      Fees are computed on the basis of the work to be performed as set by resolution of the board.  (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 441, 1985)   

      902.1 Appliance emissions.
      Section 902.1 of the UMC is amended to read as follows:
      No person shall install any wood burning stove or fireplace insert that emits more than the emission standards set by this section. A permit shall not be issued to any person who wishes to install a wood burning stove or fireplace insert that does not meet the emission standards of this section.
      A. Each wood burning stove or fireplace insert shall bear a certification from the manufacturer that the appliance meets the emission standards set forth in this section.
      B. Wood burning stove and fireplace inserts certified to meet the emission standards set by United States Environmental Protection Agency under 40 CFR Part 60 are deem in compliance with the requirements of this section.
      C. For wood burning stoves and fireplace inserts the minimum emissions are as follows: For non-catalytic appliances the emissions shall not exceed 7.5 grams, for catalytic equipped appliances the emissions shall not exceed 4.1 grams.
      Any person failing to provide the statement required under this section or installing a wood burning heater, stove, or fireplace insert without a permit is guilty of a misdemeanor pursuant to section 20.800.090. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 675, 1994; Ord. 641, 1994; Ord. 502, 1990; Ord. 489, 1989)

 

UNIFORM PLUMBING CODE REVISIONS

     102.2.7 Engineered private sewage system.
     Subsection 102.2.7 is added to read as follows:
     If a private sewage disposal system needs or requires an engineered design because of high ground water or percolation problems, an application for its approval must be submitted to the State of Nevada Bureau of Health Protection. After the application and the engineered system are approved by the State of Nevada Bureau of Health Protection, the applicant must secure a letter of approval from the agency. Upon submitting the letter of approval to the building official, the permit for the structure may be issued. Only after the State of Nevada Bureau of Health Protection has issued a written approval for the completion of the engineered system, the building official may issue a certificate of occupancy for the structure it serves. Douglas County assumes no responsibility whatsoever for the engineered system. (Ord. 1131, 2005)


      102.2.8 Appeals. The building official’s determination of the suitability of alternate materials or other means of construction may be appealed to the building and fire board of appeals in accordance with section 20.810.040. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 558, 1992; Ord. 439, 1985)

      103.11 Permit required.
      Section 103.11 of the UPC is amended by adding the following language:
      A separate permit is not required under this code if a valid building permit has been issued under the IBC or IRC for the permitted structure. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 558, 1992; Ord. 439, 1985)

      103.4.1 Fees.
      Section 103.4.1 of the UPC is amended by deleting the schedule of fees and substituting the following language:
      Plumbing permit fees must be computed on the basis of the work to be performed as set by resolution of the board. (Ord. 1131, 2005; Ord. 802, 1998; Ord. 711, 1995; Ord. 439, 1985)

      603.1 Approval of devices or assemblies.
      Section 603.1 of the UPC is amended to read as follows:
      The owner of the premises or the responsible person shall have the backflow prevention assembly tested by a certified backflow assembly tester at the time of installation, repair or relocation and at least annually thereafter unless required more frequently by the water purveyor, or utility and/or the State Health Department. The periodic testing shall be performed in accordance with procedures referenced in the University of Southern California manual of Cross-Connection Control (Ninth Edition) by a tester qualified in accordance with those standards and with the standards in the CA-NV section of the AWWA backflow prevention assembly testers and cross-connection control program. (Ord. 1131, 2005)

      604.6 Materials.
      Section 604.6 of the UPC is amended as follows:
      All malleable iron water fittings shall be galvanized. All galvanized water pipe and fittings shall be kept at least six (6) inches above final grade. (Ord. 1131, 2005)

      608.2 Excessive water pressure.
      Section 608.2 of the UPC is amended to read as follows:
      Where local static water pressure is in excess of sixty-five (65) pounds per square inch (448 kPa), an approved type pressure regulator preceded by an adequate strainer shall be installed and the static pressure reduced to sixty-one (61) pounds per square inch (421 kPa) or less. Where pressure regulators are required, the pressure regulator shall be installed between the source of water and after the meter and back-flow prevention device (if installed at the meter), and before all exterior and interior fixtures and outlets.

      For potable water services up to and including one and one-half (1-1/2) inch (40 mm) regulators, provision shall be made to prevent pressure on the building side of the regulator from exceeding main supply pressure. Approved regulators with integral bypasses shall be acceptable. Each such regulator and strainer shall be accessibly located and shall have the strainer readily accessible for cleaning without removing the regulator or strainer body or disconnecting the supply piping. Pressure regulators shall not be the type that can be adjusted to provide static water pressure more than seventy-five (75) pounds per square inch (518 kPa). All pipe size determinations shall be based on eighty (80) percent of the reduced pressure when using Table 6-5. (Ord. 1131, 2005)

      609.1 Installation.
      Section 609.1 of the UPC is amended to read as follows:
      All water piping shall be adequately supported in accordance with Section 314.0. Burred ends shall be reamed to the full bore of the pipe or tube. Changes in direction shall be made by the appropriate use of fittings, except that changes in direction in copper tubing may be made with bends, provided that such bends are made with bending equipment which does not deform or create a loss in the cross-sectional area of the tubing. Changes in direction are allowed with flexible pipe and tubing without fittings in accordance with the manufacturer's installation instructions. Provisions shall be made for expansion in hot-water piping. All piping, equipment, appurtenances, and devices shall be installed in a workmanlike manner in conformity with the provisions and intent of the code. All water service yard piping shall be at least six (6) inches below the average local frost depth. (Ord. 1131, 2005)

      610.1 Size of potable water piping.
      Section 610.1 of the UPC is amended to read as follows:
      The size of each water meter and each potable water supply pipe from the meter or other source of supply to the fixture supply branches, risers, fixtures, connections, outlets, or other uses shall be based on the total demand and shall be determined according to the methods and procedures outlined in this section. The size of pipes from the hot water heater and all hot water branches shall not exceed the minimum size necessary to meet the water supply requirements, as outlined in this section. Other than systems sized by the use of Table 6-5, the system shall be designed to assure that the maximum velocities allowed by the code and the applicable standard are not exceeded. (Ord. 1131, 2005)

      610.7 Water pipe sizing.
      Section 610.7 of the UPC is amended to read as follows:
      610.7 On any proposed water piping installation sized using Table 6-5, the following conditions shall be determined:
      1. Total number of fixture units as determined from Table 6-4, Equivalent Fixture Units, for the fixtures to be installed.
      2. Developed length of supply pipe from meter to most remote outlet.
      3. Difference in elevation between the meter and other source of supply and the highest fixture or outlet.
      4. Pressure in the street main or other source of supply at the locality where the installation is to be made.
      5. In localities where there is a fluctuation of pressure in the main throughout the day, the water piping system shall be designed on the basis of the minimum pressure available.
      All above determinations shall be clearly noted on the plans, specifications, drawings or a worksheet submitted to the Administrative Authority whenever pipes from the hot water heater exceed one half (½) inch in diameter. (Ord. 1131, 2005)

      717.0 Size of building sewers.
      Section 717.0 of the UPC is amended to read as follows:
      The minimum size of any building sewer shall be determined on the basis of the total number of fixture units drained by such sewer, in accordance with Table 7-8, but in no event shall be less than four (4) inches in diameter. No building sewer shall be smaller than the building drain. For alternate methods of sizing building sewers, see Appendix L. (Ord. 1131, 2005)

      1101.5 Subsoil drains.
      Section 1101.5.1 of the UPC is amended to read as follows:
      Where required by the geotechnical engineer or the building official, subsoil drains shall be provided around the perimeter of buildings having basements, cellars, or crawl spaces or floors below grade. Such subsoil drains may be positioned inside or outside of the footing, shall be of perforated or open-jointed approved drain tile or pipe not less than three (3) inches (80 mm) in diameter, and shall be laid in gravel, slag, crushed rock, approved three-quarter (¾) inch (19.1 mm) crushed recycled glass aggregate, or other approved porous material with a minimum of four (4) inches (102 mm) surrounding the pipe on all sides. Filter media shall be provided for exterior subsoil piping. (Ord. 1131, 2005)

      Chapter 15, Firestop protection, of the UPC is repealed. (Ord. 1131, 2005)

      Appendix H 106.2 Sizing formula.
      Appendix H 106.2 of the UPC is amended to read as follows:
The size of the interceptor shall be determined by the serving utility. (Ord. 1131, 2005)

 

NATIONAL ELECTRICAL CODE REVISIONS

     Article 80.2 Definitions.
     Article 80.2 of the NEC is amended by amending the following language:
     Authority having jurisdiction. The organization, office, or individual responsible for approving equipment, materials, an installation, or a procedure. (Ord. 1131, 2005)

      Electrical inspector. An individual authorized to perform electrical inspections by the building official. (Ord. 1131, 2005)

      Article 80.13 Authority.
      Article 80.13 of the NEC is amended by amending the following language:
Where used in this article, the term authority having jurisdiction shall include the building official or other individuals designated by the building official. This code shall be administered and enforced by the building official as designated by the governing authority as follows.
      1. The authority having jurisdiction shall be permitted to render interpretations of this code in order to provide clarification to its recommendations, as permitted by 90.4.
      2. When the use of electrical equipment or its installation is found to be dangerous to human life or property, the authority having jurisdiction shall be empowered to have the premises disconnected from its source of electrical supply.

The remainder of Article 80.13 will remain as adopted. (Ord. 1131, 2005)

      Article 80.15 Electrical board. Article 80.15 is repealed. (Ord. 1131, 2005)

      Article 80.19 Permits and approvals.
      Article 80.19 subsection (C) Issuance of Permits is amended by adding the following:
(3) Or such items designated in writing by the building official. (Ord. 1131, 2005)

      Article 80.19 (D) Annual permits subsection is repealed. (Ord. 1131, 2005)

      Article 80.19 (F) Inspections and approvals subsection is amended to read as follows:
      1. Upon the completion of any installation of electrical equipment that has been made under a permit, it shall be the duty of the person, firm, or corporation making the installation to notify the electrical inspector having jurisdiction, who shall inspect the work within a reasonable time.
      2. Where the inspector finds the installation to be in conformity with the statutes of all applicable local ordinances and all rules and regulations, the inspector shall issue to the person, firm or corporation making the installation a certificate of approval, authorizing the connection to be supplied of electricity. When a certificate of temporary approval is issued authorizing the connection of an installation, such certificates shall be issued to expire at a time to be stated therein and shall be revocable by the electrical inspector for cause.
      3. When any portion of the electrical installation within the jurisdiction of an electrical inspector is to be hidden from view by the permanent placement of parts of the building, the person, firm, or corporation installing the equipment shall notify the electrical inspector, and such equipment shall not be concealed until it has been approved by the electrical inspector. Where the concealment of the equipment proceeds continuously, the person, firm, or corporation installing the equipment shall give the electrical inspector due notice in advance, and inspections shall be made periodically during the progress of work.
      4. If, upon inspection, any installation is found not to be fully in conformity with the provisions of Article 80, and all applicable ordinances, rules, and regulations, the electrical inspector making the inspection shall at once forward to the person, firm, or corporation making the installation a written correction notice stating the defects that have been found to exist. (Ord. 1131, 2005)

      Article 80.19 subsection (H) Applications and extensions is repealed. (Ord. 1131, 2005)

      Article 80.23 Notice of violation, penalties.
      Article 80.23 subsection (B) Responsibility of the Authority Having Jurisdiction is repealed. (Ord. 1131, 2005)

      Article 80.25 Connection to electrical supply.
      Article 80.25 is amended to read as follows: Connections to the electrical supply shall be conformed to Article 80.25 (A) through (C).
      A. Authority. It shall be unlawful for any person, firm, or corporation to make connection to a supply of electricity or to supply electricity to any electrical equipment installation for which a permit is required or that has been disconnected or ordered to be disconnected.
      B. Special Consideration. By special permission of the authority having jurisdiction, temporary power shall be permitted to be supplied to the premises for specific needs of the construction project. The building official shall determine what needs are permitted under this prevision.
     C. Disconnection. Where a connection is made to an installation that has not been inspected, as outlined in the proceeding paragraphs of this section, the supplier of the electricity shall immediately report such connection to the authority having jurisdiction. If, upon subsequent inspection, it is found that the installation is not in conformity with the provisions of Article 80, the building official shall notify the person, firm, or corporation making the installation to rectify the defects and, if such work is not completed within (15) business days, the building official shall have the authority to cause the disconnection of the portion of the installation that is not in conformity. (Ord. 1131, 2005)

      Article 80.27 Inspector’s qualifications.
      Article 80.27 is amended to read as follows:
      A. Certification. All electrical inspectors shall be certified by a nationally recognized inspector certification program accepted by the building official. The certification program shall specifically qualify the inspector in electrical inspections. No person shall be employed as an Electrical Inspector unless that person is the holder of an electrical inspector’s certification.
      B. Experience. Electrical Inspector applicants shall demonstrate the following:
          1. Having demonstrated knowledge of the standard materials and methods used in the installation of electrical equipment.
          2. Be well versed in the approved methods of construction for safety to persons and property.
          3. Be well versed in the statutes of all related electrical work and the National Electrical Code, as approved by the American National Standard Institute.
      C. Renovation and Suspension of Authority. The building official shall have the authority to revoke an inspector’s authority to conduct inspections within a jurisdiction. (Ord. 1131, 2005)

      Article 80.29 Liability for damages.
      Article 80.29 is amended to read as follows: Article 80 shall not be construed to affect the responsibility or liability of any party owning, designing, operating, controlling, or installing any electrical equipment for damages to persons or property caused by a defect therein, nor shall Douglas County or any of its employees be held as assuming any such liability by reason of the inspection, reinspection, or other examination authorized. (Ord. 1131, 2005)

      Article 90.2 Scope.
      Article 90.2(D) of the N.E.C. is added to read as follows:
      90.2(D) Exempted work. An electrical permit shall not be required for the following:
          1. Repair or replacement of fixed motors, transformers or fixed approved appliances of the same type and rating in the same location.
          2. Temporary decorative lighting.
          3. Repair or replacement of current-carrying parts of any switch, contactor or control device.
          4. Reinstallation of attachment plug receptacles, but not the outlets.
          5. Repair or replacement of any overcurrent device of the required capacity in the same location.
          6. Repair or replacement of electrodes or transformers of the same size and capacity for signs or gas tube systems.
          7. Removal of electrical wiring.
          8. The wiring for temporary (not to exceed 90 days) theater, motion picture or television stage sets and scenery.
          9. Electrical wiring, devices, appliances, apparatus or equipment operating at less than 25 volts.
          10. Temporary Carnivals and circus equipment.
      Exemption from the permit requirements of this code shall not be deemed to grant authorization for any work to be done in violation of the provisions of this code or any other laws or ordinances of this jurisdiction. (Ord. 1131, 2005)


     Article 210.12 (B) Dwelling unit bedrooms.
     Article 210.12 (B) is amended to read as follows:
     With the exception of smoke detectors, carbon monoxide detectors, and home security systems installed on individual branch circuits, all branch circuits that supply 125-volt, single- phase, 15-and 20-ampere outlets installed in dwelling unit bedrooms shall be protected by an arc-fault circuit interrupter to provide protection of the entire branch circuit. (Ord. 1131, 2005)

      Article 230.2 Number of services.
      Article 230.2 is amended to read as follows:
      With the exception of 230.4, a building or other structure served shall be supplied by only one service unless permitted in Article 230.2 (A) through sets of conductors, 1/0 AWG and larger, running to the same location and conducted together at the supply end shall be considered to be supplying one service. (Ord. 1131, 2005)

      Article 230.4 Residential or agricultural properties.
      Article 230.4 is added to read as follows:
      Residential or agricultural properties determined to be one-acre or less shall only be supplied by one service, unless special permission has been granted by the building official.
Exception: An accessory dwelling approved by the County, with the electrical service installed per Article 230.63 and 230.64. (Ord. 1131, 2005)

      Article 230.63 Group.
      Article 230.63 is added to read as follows:
      Multiple services, which supply more than one building or structure on the same property, shall be grouped together with a distance between panels not to exceed 10-feet of separation.
     Exception: As determined by the building official, commercial or industrial properties with multi structures where each structure is supplied by a separate service may not be required to have all services centrally located and grouped. (Ord. 1131, 2005)

      Article 230.64 Identification.
      Article 230.64 is added to read as follows:
      Service equipment that is grouped in centralized locations to comply with Article 230.63 shall have a permanent affixed plaque identifying the structure or equipment served. The disconnecting means shall be readily identified by a 6-inch equilateral triangle, red in color that complies with the Fire Code, as adopted by the County. (Ord. 1131, 2005)

      Article 230.70(A) Service equipment-disconnecting means.
      Article 230.70(A) of the NEC is amended to read as follows:
      The service disconnection means shall be installed at a readily accessible location physically attached to the exterior of a building or structure nearest to the point of entrance of the service conductors. Multiple services shall comply with Articles 230.63 and 230.64.

      Exception #1: Manufactured housing, as regulated by NRS 489 and NEC Article 550. When the disconnecting means is mounted independently of the manufactured structure, it shall be readily identified by a six-inch (6) equilateral triangle, red in color that complies with the Fire Code.

      Exception #2: The disconnecting means may be mounted independently of the structure served, when mounted in direct line of sight, but no greater than 50-feet from the structure, and the independent disconnecting means is identified by a red triangle that complies with the Fire Code. (Ord. 1131, 2005)

      Article 680.73 Accessibility.
      Article 680.73 is amended to read as follows:
Hydromassage bathtub electrical equipment access shall be on the same floor level as the bathtub. The electrical equipment shall be accessible without damaging the building structure or interior and exterior building finish, no access shall be allowed through the underfloor. (Ord. 1131, 2005)

INTERNATIONAL FIRE CODE REVISIONS

      101.2  Intent.
      Section 101.3 of the IFC is deleted and amended substituting the following language:
      The purpose of this code is to prescribe regulations consistent with nationally recognized good practice in the area of the hazards of fire and explosion arising from the storage, handling and use of hazardous substances, materials and devices, as well as the use or occupancy of buildings or premises